Data Center & ESS Power Safety Platform

A system that monitors signs of fire and electrical leakage in electrical rooms of data centers and large buildings via SCADA, using self-powered sensors and an insulation monitoring device

01Why it is needed

In distribution panels of data center and ESS electrical rooms, overheating of breakers and joints and electrical leakage lead to major failures.

Signs of fire must be detected early without running new wiring to every panel.

  • Fixed-temperature fire detection sensor data from electrical room panels displayed on screen
  • Up to 999 sensors registered, unique IDs with no radio interference
  • An abnormal signal is generated when insulation resistance falls below the reference value due to leakage
  • Real-time monitoring of wireless sensor events in SCADA via a dedicated monitoring panel

02System configuration

Temperature sensorTemperature sensor80 ℃ alarm
Door sensorDoor sensorPanel opening
Insulation monitoring deviceInsulation monitoring deviceIMD1000
RepeaterRepeaterMWSR2-900
Signal MonitorSignal MonitorMWSM-700
SCADASCADAControl room monitoring

Ranges are based on open field with no obstacles. Each added repeater extends the range by approx. 1 km.

03Products · specifications

Fixed-temperature Fire Detection Sensor — SMA standard type

Fixed-temperature Fire Detection Sensor — SMA standard type

Model MWSF-100

SizeW77 × D56 × H47.7 mm
Weight82 g
Frequency920.700 MHz (FSK)
Transmission rangeapprox. 100 m (open field)
Operating temperatureapprox. 75 – 85 ℃ or above
PowerSelf-powered (no battery)
Dust · water protectionIP57
Insulation monitoring device

Insulation monitoring device

Model IMD1000

PurposeInsulation monitoring
System voltageAC 0 – 790 V, DC 0 – 1,000 V
Voltage extensionAC max. 1,150 V / DC max. 1,725 V
CommunicationRS-485 (Ethernet option)
History managementSystem / Alarm 255 each
Repeater

Repeater

Model MWSR2-900

SizeW115 × D115 × H30 mm
Weight167 g
Frequency920.7 / 447.9 MHz (FSK)
AntennaExternal antenna × 2
Tx/Rx rangeapprox. 1 km (open field)
Range extension+approx. 1 km (open field)
DisplayFND 3-digit, LED (Rx · Tx · Power)
PowerDC 12 V 1 A adapter
Signal Monitor

Signal Monitor

Model MWSM-700

SizeW258 × D107 × H34 mm
Weight497 g
Frequency920.7 / 447.9 MHz (FSK)
AntennaExternal antenna × 2
Reception rangeapprox. 1 km (open field)
ID registrationmax. 999
Signal storageUp to 10 overlapping signals
DisplayFND 5-digit LED
External terminalsRS-485, beacon light, speaker, power
PowerDC 12 V 1 A adapter

Digital dedicated monitoring panel

Model —

SizeW600 × D2,000 × H600 mm
Data collection unitBuilt-in Signal Monitor
Data processing unitIED (IEC 61850)
DC supply voltageDC 125 V
AC supply voltageAC 220 – 380 V (60 Hz)
NetworkGOOSE Optical communication (100 Mbps)

04Case studies

Data center · ESS distribution panels

Fire detection at breakers and joints of distribution panels, door open/close detection on key distribution panels and emergency bells for emergency notification are installed, and power safety is monitored over a SCADA network via IEDs.

Data center · ESS distribution panels
Data center · ESS distribution panels

Installation sites

  • Data center electrical rooms
  • ESS distribution panels
  • Electrical rooms of large buildings

05Benefits

01Benefits

Early detection of fire signs and activation of emergency and event alarms

02Benefits

SCADA integration via a dedicated monitoring panel with a built-in data collection unit (Signal Monitor)

03Benefits

Insulation monitoring on the same screen

CONTACT MPIA

Data Center & ESS Power Safety Platform

A system that monitors signs of fire and electrical leakage in electrical rooms of data centers and large buildings via SCADA, using self-powered sensors and an insulation monitoring device